Schneider Electric Pack – Electrical protection for 7 kW Single-Phase Charging Station

SKU 061.1 - 061.2 Category ELECTRICAL MODULES
logo

Schneider Electric Pack – Electrical protection for 7 kW single-phase charging station.


This product must be installed by a certified EVSE professional in accordance with the regulations in force in the country of installation.

Share

This pack includes:

1 Schneider IlD RCCB Residual Current Device Type A – 1P+N – 40A – 30mA
1 Schneider Thermal-Magnetic Circuit Breaker 1P+N – 40A – Curve C

Schneider Electrical Protection Pack for 7 kW Single-Phase EV Charger

The following protective devices are mandatory and must be installed on a dedicated circuit.

Protection devices required for single-phase connection:
Residual current device 40A – Type A or Hpi – 1P+N – 30mA
Circuit breaker 40A – Curve C

1/ Schneider 40A Single-Phase Residual Current Device (RCD)

The Schneider IlD RCCB – Type A – 1P+N – 40A – 30mA is essential for any EV charger installation.

It compares the incoming and outgoing current and instantly disconnects the circuit if the differential exceeds 30mA. This ensures personal protection against electric shock.

Compatibility
This RCD is compatible with all single-phase EV chargers operating with a charging current between 1A and 32A.

It must be installed in conjunction with a circuit breaker.

Installation
The device must be installed on a dedicated line specifically reserved for the EV charger, downstream of the main RCD in the electrical panel.

The EV charger must have its own dedicated circuit, protected by its own circuit breaker and residual current device.

Main specifications:
Type: A
Poles: 1P+N
Rated current: 40A max
Residual current sensitivity: 30mA

2/ Schneider 40A Circuit Breaker

The Schneider thermal-magnetic circuit breaker – 1P+N – 40A – Curve C is essential for any EV charger installation. It protects the installation against overcurrent and short circuits.

Its Curve C is specifically suited to high inrush current devices such as EV charging stations. Its high breaking capacity and fast tripping mechanism guarantee safety, reliability, and long service life.

Compatibility
This circuit breaker is suitable for EV chargers configured between 6A and 32A.

It must be used in combination with a residual current device (fully compatible with the Schneider IlD RCCB).

Installation
The circuit breaker must be installed in the distribution board, on the dedicated RCD line for the EV charger. The charger must be wired on its own protected circuit with its own breaker and RCD.

This breaker is fully compatible with the Schneider IlD RCCB.

Main specifications:
Number of poles: 1P+N
Voltage: 230V
Rated current: 40A
Breaking capacity: 4.5–6kA

Dedicated Circuit and Mandatory Electrical Protection

A Wallbox EV charging station must be installed on a dedicated circuit, with its own circuit breaker and its own residual current device (RCD). The main specifications to be taken into account when selecting the electrical protection devices are set out below:

Single-phase installation:

  • Residual Current Device (RCD): Type B, 30mA, 2P or 1P+N. A Type A or Type F RCD may be used instead of a Type B RCD when the charging station is equipped with an appropriate 6mA DC residual current detection device, ensuring disconnection of the power supply in the event of a continuous DC residual fault current exceeding 6mA.
  • Circuit breaker: Minimum Type C tripping characteristic, with a breaking capacity suitable for the installation, 2P or 1P+N. Its rated current must be determined according to the rated current or the maximum configured charging current of the charging station, as well as the characteristics of the circuit.

Three-phase installation:

  • Residual Current Device (RCD): Type B, 30mA, 4P. A Type A or Type F RCD may be used instead of a Type B RCD when the charging station is equipped with an appropriate 6mA DC residual current detection device, ensuring disconnection of the power supply in the event of a continuous DC residual fault current exceeding 6mA.
  • Circuit breaker: Minimum Type C tripping characteristic, with a breaking capacity suitable for the installation, 4P or 3P+N. Its rated current must be determined according to the rated current or the maximum configured charging current of the charging station, as well as the characteristics of the circuit.

Connection Cable Cross-Sections

The cable sizes below are provided as minimum reference cross-sections for the configurations indicated. They provide an initial guideline for connecting an EV charging station:

  • 16A Wallbox charging station or 16A socket outlet: minimum reference cross-section 2.5mm²
  • 32A Wallbox charging station: minimum reference cross-section 10mm²
  • 63A Wallbox charging station: minimum reference cross-section 16mm², subject to verification according to the installation characteristics

The final sizing of the circuit must, however, be determined according to the actual characteristics of the installation. The required conductor cross-section depends in particular on the current, circuit length, installation method, ambient temperature, number of loaded conductors, applicable correction factors and permissible voltage drop.

A conductor cross-section greater than the values indicated above may therefore be required, particularly for long cable runs or specific installation conditions.

Connection Cable Cross-Sections – NF C 15-100 and NF C 15-100-7-722

Charging Station or Socket Outlet

Rated current: 16A
Circuit breaker rating: 20A
Minimum reference cross-section: 2.5mm²

Charging Station

Rated current: 32A
Circuit breaker rating: 40A
Minimum reference cross-section: 10mm²

Charging Station

Rated current: 63A
Circuit breaker rating: To be sized according to the installation
Minimum reference cross-section: 16mm² minimum*

* For a charging station operating at 63A, a 16mm² conductor cross-section is provided as an indicative minimum value and must not automatically be associated with an 80A circuit breaker. The rating of the protective device and the conductor cross-section must be determined together according to the actual characteristics of the installation. A larger conductor cross-section may be required.

Important

The values provided above are general sizing guidelines and do not replace a detailed assessment of the electrical installation.

In accordance with the requirements of NF C 15-100 and NF C 15-100-7-722, the power supply to an EV charging station must be provided by a dedicated circuit. The sizing of the cables and protective devices must be determined according to the rated current of the charging station or its maximum configured charging current, as well as the specific characteristics of the installation.

The installer must verify, in particular, the cable run length, installation method, voltage drop, thermal conditions, permissible current-carrying capacity of the conductors and required breaking capacity before determining the final conductor cross-section and ratings of the electrical protective devices.

The installation and connection of an EV charging station must comply with all applicable regulations and standards.
This information is provided for guidance only and is not a substitute for advice from a qualified professional electrician.