Schneider Electric Pack – Electrical Protection for 11 kW Three-Phase Charging Station
SKU 065.1 - 065.2 Category ELECTRICAL MODULES
Schneider Electric Pack – Type A electrical protection for three-phase charging station rated at 11 kW.
This product must be installed by a certified EVSE professional in accordance with the regulations in force in the country of installation.
Share
Pack contents
Dedicated line and mandatory electrical protections
Pack contents
This pack includes:
1 Schneider Acti9 iID Residual Current Device Type A – 3P+N – 25A – 30mA
1 Schneider Acti9 iC Thermal-Magnetic Circuit Breaker 3P+N – 20A – Curve C
Schneider Electrical Protection Pack for 11 kW Three-Phase EV Charger with DC leakage current detection.
The following protective devices are mandatory and must be installed on a dedicated line.
Required protection for three-phase connection:
Residual current device 25A – Type A or Hpi – 3P+N – 30mA
Circuit breaker 20A – Curve C – 3P+N – Breaking capacity 10kA
1/ Schneider 25A Three-Phase Residual Current Device (RCD)
The Schneider Acti9 iID Type A – 3P+N – 25A – 30mA is essential for any EV charger installation.
It compares the incoming and outgoing current and disconnects the circuit if the difference exceeds 30mA. This function protects users from electric shock.
Compatibility
This RCD is compatible with all three-phase charging stations on the market with a charging current between 1A and 20A and equipped with a built-in DC leakage current detector.
It must be used in conjunction with a circuit breaker.
Installation
It must be installed on a line dedicated specifically to the charging station, downstream of the main RCD in the electrical panel.
The charger must have its own dedicated line, with its own circuit breaker and its own residual current device.
Main specifications:
Type: A
Poles: 3P+N
Rated current: max 25A
Residual current sensitivity: 30mA
2/ Schneider 20A Three-Phase Circuit Breaker
The Schneider Acti9 iC Thermal-Magnetic Circuit Breaker – 3P+N – 20A – Curve C is essential for any charger installation. It protects the system against overvoltage and short circuits.
Its Curve C is suited for high inrush current equipment such as EV charging stations. Its high breaking capacity and fast trip mechanism provide high levels of safety, reliability, and long service life.
Compatibility
This breaker is suitable for a charger configured between 6A and 16A.
It must be used in conjunction with a residual current device (it is compatible with the Schneider Acti9 iID).
Installation
It must be installed in the distribution panel, on the line protected by the dedicated RCD for the charger. The charger must have its own dedicated line, with its own breaker and RCD.
This breaker is fully compatible with the Schneider Acti9 iID.
Main specifications:
Number of poles: 3P+N
Voltage: 400V
Rated current: 20A
Breaking capacity: 6–10kA
Curve: C
Dedicated line and mandatory electrical protections
Dedicated Circuit and Mandatory Electrical Protection
A Wallbox EV charging station must be installed on a dedicated circuit, with its own circuit breaker and its own residual current device (RCD). The main specifications to be taken into account when selecting the electrical protection devices are set out below:
Single-phase installation:
- Residual Current Device (RCD): Type B, 30mA, 2P or 1P+N. A Type A or Type F RCD may be used instead of a Type B RCD when the charging station is equipped with an appropriate 6mA DC residual current detection device, ensuring disconnection of the power supply in the event of a continuous DC residual fault current exceeding 6mA.
- Circuit breaker: Minimum Type C tripping characteristic, with a breaking capacity suitable for the installation, 2P or 1P+N. Its rated current must be determined according to the rated current or the maximum configured charging current of the charging station, as well as the characteristics of the circuit.
Three-phase installation:
- Residual Current Device (RCD): Type B, 30mA, 4P. A Type A or Type F RCD may be used instead of a Type B RCD when the charging station is equipped with an appropriate 6mA DC residual current detection device, ensuring disconnection of the power supply in the event of a continuous DC residual fault current exceeding 6mA.
- Circuit breaker: Minimum Type C tripping characteristic, with a breaking capacity suitable for the installation, 4P or 3P+N. Its rated current must be determined according to the rated current or the maximum configured charging current of the charging station, as well as the characteristics of the circuit.
Connection Cable Cross-Sections
The cable sizes below are provided as minimum reference cross-sections for the configurations indicated. They provide an initial guideline for connecting an EV charging station:
- 16A Wallbox charging station or 16A socket outlet: minimum reference cross-section 2.5mm²
- 32A Wallbox charging station: minimum reference cross-section 10mm²
- 63A Wallbox charging station: minimum reference cross-section 16mm², subject to verification according to the installation characteristics
The final sizing of the circuit must, however, be determined according to the actual characteristics of the installation. The required conductor cross-section depends in particular on the current, circuit length, installation method, ambient temperature, number of loaded conductors, applicable correction factors and permissible voltage drop.
A conductor cross-section greater than the values indicated above may therefore be required, particularly for long cable runs or specific installation conditions.
Connection Cable Cross-Sections – NF C 15-100 and NF C 15-100-7-722
Charging Station or Socket Outlet
Rated current: 16A
Circuit breaker rating: 20A
Minimum reference cross-section: 2.5mm²
Charging Station
Rated current: 32A
Circuit breaker rating: 40A
Minimum reference cross-section: 10mm²
Charging Station
Rated current: 63A
Circuit breaker rating: To be sized according to the installation
Minimum reference cross-section: 16mm² minimum*
* For a charging station operating at 63A, a 16mm² conductor cross-section is provided as an indicative minimum value and must not automatically be associated with an 80A circuit breaker. The rating of the protective device and the conductor cross-section must be determined together according to the actual characteristics of the installation. A larger conductor cross-section may be required.
Important
The values provided above are general sizing guidelines and do not replace a detailed assessment of the electrical installation.
In accordance with the requirements of NF C 15-100 and NF C 15-100-7-722, the power supply to an EV charging station must be provided by a dedicated circuit. The sizing of the cables and protective devices must be determined according to the rated current of the charging station or its maximum configured charging current, as well as the specific characteristics of the installation.
The installer must verify, in particular, the cable run length, installation method, voltage drop, thermal conditions, permissible current-carrying capacity of the conductors and required breaking capacity before determining the final conductor cross-section and ratings of the electrical protective devices.
The installation and connection of an EV charging station must comply with all applicable regulations and standards.
This information is provided for guidance only and is not a substitute for advice from a qualified professional electrician.